SolarAPP+ Eligibility Checklist
|
SolarAPP PV Eligibility 4/26/2021 |
|
System |
|
New Rooftop Residential PV Systems Only |
|
Installed by contractor with all licenses required by jurisdiction |
|
No building integrated solar systems |
|
Electrical |
|
Limited to 2017 NEC |
|
600V Max per DC System Size |
|
Single phase only |
|
No Aluminum Wires |
|
Must Use 600V rated PV wire (due to outer diameter > 0.24" (6.1mm)) |
|
Must use 90 deg C rated insulated wire |
|
Height of rooftop conduit > = 7/8" |
|
Max 2 DC strings in parallel |
|
Max 9 current carrying conductors in a raceway |
|
Inverter output circuit conductors must be THWN-2, or listed NM |
|
Terminals must be rated to 75 deg C, labeled for use with Cu wires, and accept minimum 8 AWG wire |
|
If using microinverter, 1 module per microinverter |
|
Permitted to install on up to or equal to 400A Service |
|
Permitted to install on up to or equal to 225A Service Disconnect |
|
Permitted to install on up to or equal to 225A busbars |
|
No existing PV on site |
|
May install only 1 module type |
|
May install only 1 racking system type |
|
May install up to 2 Inverters for String Inverters, up to 1 inverter type for Micro-inverters and AC modules Systems |
|
Conduit may not be Schedule 80 PVC |
|
Single Family Dwelling Only |
|
Modules and Inverters must be listed on CEC |
|
Rapid Shutdown cannot be satisfied using the method: No exposed wiring or conductive parts [690.12(B)(2)(3)] |
|
Flat Plate PV Modules Only |
|
No trenching allowed |
|
All power production inverter outputs have the same point of connection |
|
Structural |
|
2018 IBC |
|
PV system + hardware weight is less than or equal to 4psf |
|
Limited to 10” above the roof for pitched (>2/12) roof |
|
No metal roof or low-slope roof in areas with > 15psf snow load |
|
No wood shake or wood shingle roofing |
|
No carports or non-permanent structures |
|
No ground mounted systems |
|
Only one type of mounting hardware system per project |
|
Fire |
|
2018 IRC |